Noise

Heat pump noise: the 37 dB(A) rule and how to site a unit

How loud a heat pump is for the neighbours is not a matter of opinion in England: it is a calculation with a limit. Here is how the calculation works, how far away a unit needs to be for typical sound levels, and what to do about noise beyond the rule.

Figures checked 8 October 2026 Sources listed at the end Published by an independent guide, not an installer

Are heat pumps noisy?

Not usually enough to matter, and in England the rules make sure of it. To be permitted development, the calculated sound level from the outdoor unit at the nearest neighbour’s habitable room must not exceed 37.0 dB(A) under the MCS planning standard. That is a calculated level at the window, not a reading at the unit: the unit itself can be louder close up. Position, distance and any barrier decide the answer, and the calculator below shows how. In terraces and flats, where neighbours are close, the calculation is the first thing to check; the guide to heat pumps for flats covers those cases.

The limit and what it measures

The noise rule that matters for most homeowners in England sits in MCS 020 a), the Microgeneration Certification Scheme’s standard for air source heat pump sound calculation for permitted development installations. Issue 1.1 is dated 14 April 2025. It sets out a calculation that confirms whether the permitted development noise limit of 37 dB LAeq,5mins, shown in the standard’s checklist as 37.0 dB(A), would be met. The Order itself is covered in heat pump planning permission; this page is about the noise condition.

Three details of the definition are worth knowing:

  • Where it is measured. At an “assessment position”: 1 metre outside the centre point of any door or window to a habitable room of a neighbouring property, measured at right angles to the plane of the door or window. The effect of the facade is ignored.
  • Which rooms count. Rooms used or intended for sleeping or living, but not rooms used solely for cooking, bathrooms, corridors, laundry rooms, hallways or utility rooms.
  • Which neighbours count. Any building used as a dwelling, hotel or residential institution. Where the unit goes on a block of flats, other flats in the same block count, but not the owner’s own flat.

The installer must do one calculation for each assessment position that could be affected, keep one copy and give you another. That is a document you are entitled to ask for before you pay a deposit, and it is a good test of how seriously an installer takes siting. The standard adds that installers are under a duty to ensure compliance for any installation done as permitted development, MCS may impose penalties if they do not, and an installation that fails the standard may be subject to enforcement action by the local planning authority.

Where the unit goes is a planning question as much as a noise one: heat pump planning permission sets out the permitted development limits and when the noise calculation decides the answer. Siting it further from the house adds pipework, which is one of the line items on the heat pump installation cost page.

The calculation, step by step

MCS 020 a) is a short desktop calculation. The eight steps in the standard are, in plain terms:

  1. Date. The date of the assessment is recorded, and re-checked if time passes before installation, in case a neighbouring building or barrier has changed.
  2. The assessment positions. Every potentially affected window or door, on all sides and at each floor. The nearest is not always the loudest: a further window with a clearer line of sight can come out worse.
  3. Sound power level. Taken from the manufacturer’s data. The low-noise mode figure is not permitted.
  4. Directivity (Q). A count of reflecting surfaces within 1 metre of the unit that extend at least that far beyond it in two or more directions: Q2 for one (including the ground), Q4 for two, Q8 for three. A unit with more than 3 reflecting surfaces, such as one in a small lightwell, will not meet the standard.
  5. Distance. A straight line from the centre of the unit to the assessment position, to the nearest 0.1 metre.
  6. Barrier correction. Subtracted if a solid barrier sits between the unit and the window (see the matrix below).
  7. The sound pressure level. Calculated with the formula below.
  8. The check. The result, rounded to 0.1 dB, must be equal to or lower than 37.0 dB(A) at every assessment position.

The step 7 formula is: Lp = Lw + 10 · log10(Q ÷ (4π r²)) − AB, where Lw is the sound power level in dB(A), Q the directivity factor, r the distance in metres and AB the barrier attenuation.

Try the MCS 020 a) calculation

No details needed. The defaults use the sound power from MCS’s own worked example (60 dB(A)). Change them to match a data sheet and your garden. This is indicative: the installer’s calculation for your actual position is the one that counts.

Calculated level at the window36.97 → 37.0 dB(A)

At or below the limit

Limit: 37.0 dB(A), rounded to 0.1. Formula and barrier values from MCS 020 a), Issue 1.1.

How far is far enough?

The table turns the formula round: the straight-line distance at which a unit reaches 37.0 dB(A) with no barrier, for three sound power levels and the three reflecting-surface cases. The sound power of 60 dB(A) is the value MCS uses in its own worked example; check a real unit’s figure on its energy label or the MCS product database. These are arithmetic on the published formula, not measurements.

Distance at which Lp equals 37.0 dB(A), no barrier. Calculated from the MCS 020 a) step 7 formula; illustrative. Source of formula: MCS 020 a), Issue 1.1, read 8 October 2026.
Sound power levelOne reflecting surface (Q2)Two (Q4)Three (Q8)
55 dB(A)3.2 m4.5 m6.3 m
60 dB(A)5.6 m8.0 m11.3 m
65 dB(A)10.0 m14.2 m20.0 m

Look along the rows: each extra reflecting surface adds roughly 3 dB, which is why a unit tucked into a corner needs about 1.4 times the distance of one on an open wall. Down the columns, each 5 dB of sound power adds a factor of about 1.8 to the distance needed. That is the case for choosing a lower sound power unit when the neighbour is close. A quiet unit on an open wall can pass at about three metres, as the first cell shows, while a louder unit in a corner needs several times that distance, or a barrier.

Illustrative example

A unit with a sound power of 60 dB(A) against one wall (two reflecting surfaces including the ground, Q4), 8.0 metres from a neighbour’s window with no barrier: Lp = 60 + 10·log10(4 ÷ (4π × 8²)) = 36.97, which rounds to 37.0 dB(A). That is exactly on the limit, so it complies. At 7 metres it does not. MCS’s own worked example has the same unit 8.0 metres from a first-floor bedroom window with a brick wall giving partial view (a 5 dB correction), which comes to 32.0 dB(A), and 5.0 metres from a ground-floor window with the wall blocking the view completely (10 dB), which comes to 31.0 dB(A).

Barriers, reflecting surfaces and two units

A solid barrier between the unit and the window reduces the calculated level, but only if it meets the standard’s definition. A Type 1 barrier is a solid brick or masonry wall, or a solid fence, at least 18 mm thick with no cracks or gaps, extending at least 1 metre horizontally beyond either edge of the unit. A Type 2 barrier is a solid fence thinner than that, again with no gaps. Open fences, fences with gaps, vegetation and walls in poor repair count as no barrier. The reduction depends on the view from the top edge of the unit to the window:

Barrier attenuation in dB, from MCS 020 a) Issue 1.1 step 6, read 8 October 2026. “Partial view” means the window becomes visible when moving up to 0.25 m from the top edge of the unit.
BarrierNo viewPartial viewFull view
Type 1: solid, at least 18 mm10 dB5 dB0 dB
Type 2: solid, under 18 mm5 dB2.5 dB0 dB
No barrier0 dB0 dB0 dB

Two units on a detached house are summed logarithmically at any assessment position they share: two identical units at the same level give a result 3 dB higher than one, which is why the second unit can turn a pass into a fail. The standard’s own guidance for a failed calculation is that it may be possible to make adjustments, such as moving the unit, and MCS has published separate guidance for installers on mitigating noise (18 November 2025).

Beyond the rule: vibration, nuisance and flats

Passing a 37 dB(A) calculation is not the whole story, and the best-informed source on what else matters is a joint Professional Advice Note from the Institute of Acoustics and the Chartered Institute of Environmental Health (2026). Its design advice is practical:

  • Location. Put units as far as practicable from sensitive neighbours, while keeping to the manufacturer’s clearances so airflow is not restricted.
  • Barriers. A barrier works if it breaks the line of sight and is imperforate with a mass of at least 10 kg per square metre.
  • Vibration. A unit rigidly fixed to a building can pass vibration into the structure, which re-radiates as noise indoors and can be annoying even at low levels. Use vibration isolation mounts and pipe connections.
  • Enclosures. Manufacturer-approved enclosures can reduce noise but risk air recirculation and poorer performance, so they are a last resort.
  • Your own household. Bedrooms and garden space of the house the unit serves count too, and the occupier may be a tenant rather than the owner.

The same note says cumulative impact from many units is unlikely to be a problem for detached, semi-detached and terraced houses on recent research, and is only necessary to consider for courtyards or flats; see heat pumps for flats and terraces. It also sets out alternative assessment routes for installations where permitted development does not apply for non-acoustic reasons (for example, a listed building): an installer-led MCS 020 a) calculation, then a desktop assessment by a suitably qualified acoustician against the same 37 dB(A) criterion, and a full assessment in exceptional cases such as tranquil areas.

If a complaint comes after installation, the route is different. GOV.UK says councils investigate noise that amounts to a statutory nuisance under the Environmental Protection Act 1990, and must serve an abatement notice if one exists or will occur; the notice can be delayed for up to seven days while informal resolution is attempted. Complaints about a defective installation are covered in complaints and consumer codes.

What to ask the installer

  • A copy of the completed MCS 020 a) table for each assessment position, with the sound power level and its source.
  • Where the unit will stand, how many reflecting surfaces it has and the distance to the nearest neighbouring windows, including upstairs windows.
  • What mounting is proposed: ground-mounted on a base, or wall-mounted, and what vibration isolation is used.
  • What happens if the calculation fails: a different position, a quieter model or a barrier.
  • How the noise from the unit during defrost and at maximum output has been considered, since the standard’s sound power figure is measured under standard test conditions and may not be the noisiest operating condition.

The order of events from survey to commissioning is in the installation process, and the checklist for comparing quotes is here. Source note: figures on this page come from the documents listed at the end, read on 8 October 2026.

Noise worries, answered

“They are noisy and will keep the neighbours awake.”

Government communications describe modern heat pumps as relatively quiet, with noise levels similar to a fridge or a boiler when properly installed. For planning, the law does not rely on that: in England an air source unit is only permitted development if the calculated level at a neighbour’s window or door is 37.0 dB(A) or less.

A poorly sited unit, or one mounted rigidly to a wall, can still be annoying even at modest levels. Siting and mounting decide this, not the average.

“Passing the calculation means nobody can complain.”

It does not. GOV.UK says councils must investigate noise that amounts to a statutory nuisance under the Environmental Protection Act 1990, meaning noise that unreasonably and substantially interferes with the use or enjoyment of a home, or is likely to injure health. Permitted development is a planning status and does not remove that route.

A well-sited unit that passes the calculation is unlikely to be a nuisance, but the route exists.

“I can use low-noise mode and get through the test.”

The standard rules this out. For the calculation the installer must use the sound power level from the manufacturer’s data and must not use the sound power level in “low noise mode”.

Low-noise mode is still useful for quieter operation at night; it simply is not counted in the planning calculation.

Questions people ask

What is the noise limit for a heat pump in England?

37.0 dB(A) (written 37 dB LAeq,5mins in the standard), calculated at an assessment position one metre outside the centre of a door or window to a habitable room of a neighbouring property, ignoring the effect of the facade. It comes from MCS 020 a), Issue 1.1. The earlier 42 dB(A) figure belongs to the superseded standard.

What counts as a habitable room?

MCS 020 a) defines it as any room used or intended to be used for sleeping or living which is not solely used for cooking, and excludes bath or toilet facilities, service rooms, corridors, laundry rooms, hallways and utility rooms. A neighbouring property is any building used as a dwelling, hotel or residential institution, including a flat in the same block.

Does the heat pump have to be silent?

No. The limit is a calculated level at a specific point, not a level at the unit. A unit can be considerably louder at its own casing than at the neighbour’s window, because sound level falls with distance. That is why siting counts for more than the headline figure on the data sheet.

Where do I find a heat pump’s sound power level?

The standard says it should be taken from the manufacturer’s data: the product fiche, the product energy label or the MCS product database. It must be the sound power level, not a sound pressure level quoted at some distance, and not the low-noise mode figure. If a datasheet just says “noise level”, the standard says to ask the manufacturer which it is.

What if my installation fails the calculation?

Then it is not permitted development in that position. MCS says it may be possible to move the heat pump so that it complies, and has published guidance on mitigating noise for installers; otherwise you would apply for planning permission, which the planning guide explains.

Sources for the figures on this page

  1. MCS — MCS 020 a) air source heat pump sound calculation, Issue 1.1 (14 April 2025)
  2. MCS — installation guidance on mitigating heat pump noise (news item, 18 November 2025)
  3. Institute of Acoustics and CIEH — Domestic Air Source Heat Pumps Professional Advice Note (2026)
  4. GOV.UK — noise nuisances: how councils deal with complaints
  5. GOV.UK Clean Energy — install a heat pump
  6. legislation.gov.uk — GPDO 2015 Schedule 2 Part 14 Class G

Read on 8 October 2026 unless the source line says otherwise. Scheme rules change: if a figure here disagrees with GOV.UK or Ofgem, the official page is right — tell us through the form and we will correct it.

Ask us about your heat pump grant

Tell us about the property and what heats it now. Your enquiry comes to SEO-DONS LTD, the publisher of this guide, and we reply by email. We are not an installer, Ofgem or the government. Check any installer on the MCS register before you sign.

What happens next

  1. Your enquiry arrives with SEO-DONS LTD, the publisher of this guide.
  2. We read it and reply by email, usually with the next step for your situation.
  3. If you want quotes, compare at least three written quotes from MCS-certified installers. There is no obligation to go ahead.
Add a little more detail (optional — helps the right firm reply)

Your enquiry comes to SEO-DONS LTD, the publisher of this guide, and we reply by email. This site is an independent guide — not an installer, assessor or scheme administrator. See our privacy notice.

Check eligibility Get quotes
Request quotes