Heat pump efficiency: COP, SCOP and SPF explained

Efficiency is the number heat pump sales talk leans on, and it is easy to misread. This guide explains COP, SCOP and SPF, shows what a large UK field trial actually measured, and turns the ratios into bill arithmetic.

Figures checked 8 October 2026 Sources listed at the end Published by an independent guide, not an installer

COP, SCOP and SPF

All three describe how much heat a heat pump delivers for each unit of electricity. The Energy Saving Trust defines the Coefficient of Performance (CoP) as the heat produced per unit of electricity used, so a CoP of 3.0 means three units of heat for one of electricity. Every heat pump has a published datasheet CoP, measured under specific test conditions.

Real homes are not a test rig. Outside temperature changes through the year, and the heat pump works harder when it is colder. So the Trust points to the Seasonal Coefficient of Performance (SCoP) or Seasonal Performance Factor (SPF), which averages efficiency across the whole year. It adds that installers must calculate the SPF from the system design for your home, using the average temperatures at your location and the size of your radiators, and should share the calculation before work starts.

TermWhat it measuresUse it for
COPHeat out per unit of electricity at one test conditionComparing machines on a datasheet
SCOP / SCoPSeasonal average across a typical yearPredicting running cost for your design
SPFSeasonal performance factor, averaged over a yearJudging how the system actually performed

The glossary entries are on the glossary page, and the broader mechanism is in how a heat pump works.

What homes actually achieve

The Energy Systems Catapult Electrification of Heat project installed 742 heat pumps and monitored them for a year. Among 428 air source units, the median SPFH2 was 2.93 (interquartile range 2.67 to 3.19) and the median on a second measure, SPFH4, was 2.78 (range 2.55 to 3.05). The report also cites an earlier trial, the Renewable Heat Premium Payment scheme, at 2.44 on the SPFH4 basis. The Energy Saving Trust, using its own wording, says typical systems come out at around 3.1.

Two cautions from the same report. In 91.9% of properties the in-situ SPFH2 was below the designed SCOP, with a median gap of 17.9%. And there was no significant difference in SPF by house type or age. In other words, the gap between design and reality is mostly about the system and how it is run, not the age of the building.

Efficiency by outside temperature

Outside temperatureMedian 30-minute COP (air source)
10°C3.37
-3°C2.37
-5°C2.3

Source: Energy Systems Catapult, Dec 2024. The ground source median at -5°C air temperature was 3.1 in a small sample, because the ground stays warmer than the air, which is part of why ground source systems tend to be more efficient. The air source vs ground source guide sets out the cost trade-off.

Why flow temperature matters

Efficiency falls as the water temperature the heat pump must produce rises. The trial found a median COP of 3.5 when producing 35°C water, 2.38 at 55°C and 2.02 above 65°C. Across the monitored air source units the mean operating flow temperature was 39.7°C. Heat pumps include weather compensation, which lowers the flow temperature when it is milder outside, and the Energy Saving Trust says a correctly set heating curve is one of the main levers on running cost. Bigger radiators let the system run cooler, which is the reason installers propose them. The controls guide and sizing guide go deeper, and the underfloor heating guide covers the low-temperature end.

Turning efficiency into pounds

Electricity use is heat demand divided by the seasonal figure. This is an illustrative calculation, not a forecast: it takes a home needing 12,000 kWh of heat a year and the Ofgem cap electricity rate of 26.32p/kWh for 1 October to 31 December 2026, excluding standing charges.

Seasonal figureElectricity usedAnnual cost at 26.32p
2.54,800 kWh£1,263
3.04,000 kWh£1,053
3.53,429 kWh£902
4.03,000 kWh£790

Every step in efficiency matters, but so does the price of a unit. Put your own tariff into the calculator.

What your efficiency means for your bill

No details needed. Change any figure to match your own quote or bills. Results are indicative — an MCS installer’s heat-loss survey and written quote are what count.

Heat pump, per year£1,053
Gas boiler, per year£1,171

—

Difference per year at these prices.

Prices: Ofgem cap 1 October to 31 December 2026 — electricity 26.32p/kWh, gas 7.97p/kWh, gas standing charge 29.68p/day (GB average, Direct Debit); heating oil 114.8p/litre including 5% VAT (109.3p before VAT; BoilerJuice UK average for 1,000 litres, read 28 September 2026); 10.35 kWh per litre assumed. No VAT on household electricity from 1 October 2026 to 31 March 2027, which flatters heat pumps in this window. LPG prices vary too much to default — use your own bills. Illustrative, not a quote.

Ask installers for a written quote

How to read an installer’s figure

  • Ask whether the number is a datasheet COP, a calculated SCOP for your design, or a measured SPF from another home.
  • Ask for the flow temperature it assumes. A high design flow temperature means a lower seasonal figure.
  • Treat an unexplained efficiency promise as marketing. A real one comes with the heat-loss calculation behind it.
  • Compare quotes on the quotes checklist, not on the efficiency headline alone.

Questions people ask

What is the difference between COP and SCOP?

COP (Coefficient of Performance) is the heat out divided by electricity in at a specific test condition. SCOP, or seasonal COP, averages that over a whole heating season using typical temperatures. The Energy Saving Trust says the published COP does not always help work out annual cost, which is why the seasonal figure (SCoP or SPF) is the better guide.

What is a good SCOP for a heat pump?

The Energy Saving Trust says typical systems run at a seasonal performance factor of about 3.1 and a well-installed, well-managed one can exceed that, sometimes above 4. In the Energy Systems Catapult trial of 428 air source heat pumps the median SPFH2 was 2.93 and the interquartile range ran from 2.67 to 3.19.

Does a heat pump work less well in winter?

Its efficiency falls as it gets colder, because it works harder to lift heat. In the trial the median 30-minute COP was 3.37 at 10°C outside, 2.37 at -3°C and 2.3 at -5°C. It still delivers more than two units of heat per unit of electricity at those temperatures.

Why is my heat pump less efficient than the brochure says?

Published figures come from specific test conditions. The trial found 91.9% of properties had a measured seasonal figure below the designed one, with a median shortfall of 17.9%. Installation quality, flow temperature, controls and how you use the system all affect it.

How can I make my heat pump more efficient?

Run it at the lowest flow temperature that keeps the house comfortable, keep the heating on for longer rather than short high bursts, check the heating curve is set correctly, and make sure radiators are large enough. The controls guide goes through each.

Sources for the figures on this page

  1. Energy Saving Trust — heat pumps: how they work, costs and savings (read 8 October 2026)
  2. Energy Saving Trust — heat pump questions answered, 27 May 2026 (read 8 October 2026)
  3. Energy Systems Catapult — Insights from Heat Pump Performance Data, Dec 2024 (read 8 October 2026)
  4. Energy Systems Catapult — EoH Project Summary Report, Dec 2024 (read 8 October 2026)
  5. Ofgem — energy price cap unit rates

Read on 8 October 2026 unless the source line says otherwise. Scheme rules change: if a figure here disagrees with GOV.UK or Ofgem, the official page is right — tell us through the form and we will correct it.

Ask us about your heat pump grant

Tell us about the property and what heats it now. Your enquiry comes to SEO-DONS LTD, the publisher of this guide, and we reply by email. We are not an installer, Ofgem or the government. Check any installer on the MCS register before you sign.

What happens next

  1. Your enquiry arrives with SEO-DONS LTD, the publisher of this guide.
  2. We read it and reply by email, usually with the next step for your situation.
  3. If you want quotes, compare at least three written quotes from MCS-certified installers. There is no obligation to go ahead.
Add a little more detail (optional — helps the right firm reply)

Your enquiry comes to SEO-DONS LTD, the publisher of this guide, and we reply by email. This site is an independent guide — not an installer, assessor or scheme administrator. See our privacy notice.

Check eligibility Get quotes
Request quotes